Glands for Hazardous areas

A2F EExde IIC compression gland
for FLEXIBLE CABLE

Features and Benefits
• For indoor/outdoor use and hazardous areas.
• Fitted with specially formulated elastomeric displacement seal, giving superior
   cable retention, explosion protection and IP rating.
• Manufactured from high quality brass and nickel plated.
• Supplied with a polypropylene or neoprene sealing gasket.

 
Technical Data
Type  A2F
Gland Material  Brass (Nickel Plated)
Seal Material  Thermoplastic Elastomer (Silicone on request)
Cable Type  Unarmoured
Sealing Area  Outer sheath
Optional Accessories and Tools  Locknut, Shroud, Earth Tag, Adaptor /  
  Reducer
 
Standards and Certifications

Hazardous Area Classification

CENELEC / ATEX

Category 2, Category 3, EExde II 2 GD

Compliance Code

Certification No.

CENELEC / ATEX

EN60079-0 2004  EPSILON 06 ATEX 2066X
EN60079-1 2004  EPSILON 06 ATEX 2066X
Ingress Protection IP66/67/68
Operating Temperature -30°C TO +130°C

Special Conditions for Safe Use - X
Glands must be used as part of a certified assembly in surface installations only.
Not for use on Exd enclosures that are larger than 2000cm3 volume in group IIC gases in zone 1 areas.

 
 
All content copyright © 2004 - 2008  CCG Cable Terminations Pty Ltd

Unit B,Metcalfe Road - Skippers Lane Industrial Estate - Middlesbrough -TS6 6PT
Tel: 0044 (0)1642 430346   Fax: 0044 (0)1642 459196    Email: sales@ccgcablegland.co.uk