Armortex
EExd I / IIC Gland
MAC - Multi Armour Cone
|
|
Features and
Benefits
• Nickel plated brass / stainless steel gland for steel wire, tape, braided, aluminium, armoured cable
• No need to change seals or reverse cones or cone rings to
accommodate
different types of armoured cable.
• Captive cone and cone ring ensures no loose parts during
assembly.
• Extra long captive explosion proof seal ensures built in
safety.
• Armour clamp components can be inspected after installation.
• Gland can be used on Exd enclosures greater than 2 litres
volume.
|
|
|
|
|
|
| Technical
Data |
|
Type |
ARMORTEX |
|
Gland Material |
Brass (Nickel Plated), Stainless Steel
|
|
Seal Material |
Thermoplastic Elastomer |
|
Cable Type |
Steel Wire, Braid, Tape Armour |
|
Armour Clamping |
Multi Armour Cone and Cone Ring |
|
Sealing Area |
Inner and outer sheath |
|
Optional Accessories and Tools |
Shroud, Earth Tag, Adaptor / Reducer |
|
|
| Standards
and Certifications |
|
Hazardous Area
Classification |
|
|
SANS/SABS IEC |
Zone 1, 2, 21and 22
Exd I / IIC, Exe I / IIC and DIP |
|
CENELEC / ATEX |
Category 2, Category
3, EExde I / II 2 GD, EExd I M2 |
|
Compliance Code |
Certification No. |
|
CENELEC
/ ATEX |
|
|
EN50014:1997E |
DEMKO 01 ATEX 130325X EPSILON 06 ATEX 2044 |
|
EN50018:2000E |
DEMKO 01 ATEX 130325X EPSILON 06 ATEX 2044 |
|
EN50019:2000E |
DEMKO 01 ATEX 130325X EPSILON 06 ATEX 2044 |
|
EN50281-1-1:1999E |
DEMKO 01 ATEX 130325X EPSILON 06 ATEX 2044 |
|
SANS
/ SABS / IEC |
|
|
|
SANS 808 |
SABS MS/W446U |
|
SANS/SABS IEC 60079-0 |
2000 |
SABS MS/W446U |
|
SANS/SABS IEC 60079-1 |
2001 |
SABS MS/W446U |
|
SANS/SABS IEC 60079-7 |
2001 |
SABS MS/W446U |
|
SANS/SABS IEC 60529 |
1989 |
SABS MS/W446U |
|
SANS/SABS IEC
61241.1.1 |
1999 |
SABS MS/W446U |
|
CHINESE |
|
GB3638. 1-2000 part 1 |
|
CNEx09 0428U |
|
GB3638. 2-2000 part 2 |
|
CNEx09 0428U |
|
GB3638. 3-2000 part 3 |
|
CNEx09 0428U |
|
GB12476. 1-2000 |
|
CNEx09 0428U |
|
| Ingress
Protection |
IP66/67/68 |
| Operating
Temperature |
-30°C
to + 130°C |
|
Special Conditions for
Safe Use - X
Glands that incorporate a seal with an uncompressed height of less than 20mm shall not be used with EEX d IIC apparatus that has a volume in excess of 2000cc. If mounted in flame proof enclosures, make sure that at least threads are engaged and that the depth of engagement of enclosures smaller than 100
cm3 are at least 5mm and for enclosures larger than 100
cm3 at least 8mm.
|
|
|