D1EX
EExde IIC captive cone gland
MAC
- Multi Armour Cone
|
|
Features and
Benefits
• For use indoors and
hazardous areas.
• Two piece handling, no loose parts.
• Freely rotating captive cone, providing an armour clamp and
earth bond
without twisting the armour wires.
• Factory fitted captive elastomeric seals for built-in safety.
• Seals on the inner sheath of the cable.
• Manufactured from high quality brass, nickel plated and stainless steel.
• Complete with polypropylene sealing gasket.
|
|
|
|
|
|
| Technical
Data |
|
Type |
D1EX |
|
Gland Material |
Brass (Nickel Plated), Stainless Steel |
|
Seal Material |
Thermoplastic Elastomer (Silicone on request) |
|
Cable Type |
Steel Wire, Braid, Tape Armour |
|
Armour Clamping |
Multi Armour Cone and Cone Ring |
|
Sealing Area |
Inner sheath |
|
Optional Accessories |
Locknut, Shroud, Earth Tag, Adaptor / Reducer |
|
|
|
| Standards
and Certifications |
|
Hazardous Area
Classification |
|
|
SANS/SABS IEC, AS/NZS
IEC, CNEx |
Zone 1, 2, 21and 22
Exde IIC and DIP |
|
CENELEC / ATEX |
Category 2, Category
3, EExde II 2 GD |
|
Compliance Code |
Certification No. |
|
CENELEC
/ ATEX |
|
|
EN50014:1997E |
DEMKO 01 ATEX 130325X |
|
EN50018:2000E |
DEMKO 01 ATEX 130325X |
|
EN50019:2000E |
DEMKO 01 ATEX 130325X |
|
EN50281-1-1:1999E |
DEMKO 01 ATEX 130325X |
|
SANS
/ SABS / IEC |
|
|
|
SANS/SABS 1213 |
SABS S/W 449UX |
|
SANS/SABS IEC 60079-0 |
2000 |
SABS S/W 449UX |
|
SANS/SABS IEC 60079-1 |
2001 |
SABS S/W 449UX |
|
SANS/SABS IEC 60079-7 |
2001 |
SABS S/W 449UX |
|
SANS/SABS IEC 60529 |
1989 |
SABS S/W 449UX |
|
SANS/SABS IEC
61241.1.1 |
1999 |
SABS S/W 449UX |
|
AUSTRALIAN
/ NEW ZEALAND / IEC |
|
|
|
ANZEx 03.4083X |
|
AS/NZS IEC 60079-0 |
2000 |
AUS Ex 03.3844X |
|
AS/NZS IEC 60079-1 |
2002 |
AUS Ex 03.3844X |
|
AS/NZS IEC 60079-7 |
2001 |
AUS Ex 03.3844X |
|
AS
1939 |
1990 |
AUS Ex 03.3844X |
|
AS/NZS IEC 61241.1.1 |
1999 |
AUS Ex 03.3844X |
|
CHINESE |
|
GB3638. 1-2000 part 1 |
|
CNEx09 0427U |
|
GB3638. 2-2000 part 2 |
|
CNEx09 0427U |
|
GB3638. 3-2000 part 3 |
|
CNEx09 0427U |
|
GB12476. 1-2000 |
|
CNEx09 0427U |
|
| Ingress
Protection |
IP66/67/68 |
| Operating
Temperature |
-30°C
TO +130°C |
|
Special Conditions for
Safe Use - X
Glands must be used as
part of a certified assembly in surface installations only
Not for use on Exd enclosures that are larger than 2000cm3 volume
in group IIC gases in zone 1 areas
|
|
|