Glands for Hazardous areas

Posi Grip EExe compression gland
for unarmoured cable

Features and Benefits
• For use in highly corrosive and hazardous areas.
• All brass parts encapsulated in a non-corrosive body.
• Complete with a hard gripper seal, deluge proof O-ring and elastomeric 
  inner seal for complete ingress protection IP68.
• Supplied with a polypropylene gasket.

 
Technical Data
Type

POSIGRIP

Gland Material Brass encapsulated in Glass Reinforced Polyester/PBT
Seal Material

Thermoplastic Elastomer (silicone on request)

Cable Type Unarmoured
Sealing Area Outer sheath
Optional Accessories Locknut
 
Standards and Certifications

Hazardous Area Classification

IEC, SABS & AUS Ex, CNEx

 

Zone 1, 2, 21and 22 Exe IIC and DIP

CENELEC / ATEX

 

Category 2, Category 3, EExe II 2 GD


Compliance Code

 

Certification No.

CENELEC / ATEX

   

EN50014:1997E

 

DEMKO 01 ATEX 130325X

EN50019:2000E

 

DEMKO 01 ATEX 130325X

EN50281-1-1:1999E

 

DEMKO 01 ATEX 130325X

SANS / SABS / IEC

   

SANS/SABS 1213

SABS S/W 458U

SANS/SABS IEC 60079-0

2000

SABS S/W 458U

SANS/SABS IEC 60079-7

2001

SABS S/W 458U

SANS/SABS IEC 60529

1989

SABS S/W 458U

SANS/SABS IEC 61241.1.1

1999

SABS S/W 458U

AUSTRALIAN

   

AS 2380.6

 

AUS Ex 2404U

AS 1939

 

AUS Ex 2404U

NSW MDA

 

Exe 3171

CHINESE
GB3638. 1-2000 CNEx09 0429U
GB3638. 3-2000 CNEx09 0429U
GB12476.1-2000 CNEx09 0429U
Ingress Protection IP66/67/68
Operating Temperature -30°C to +130°C
 
 
All content copyright © 2004 - 2008  CCG Cable Terminations Pty Ltd

Unit B,Metcalfe Road - Skippers Lane Industrial Estate - Middlesbrough -TS6 6PT